Product Details
Ⅰ. Application
It is suitable to use for transmission and distribution electric circuit in power system with rated voltage up to 0.6/1 kV. Especially for the fields possessing precise electronic equipments.
II. Type and Designation
Type |
Designation |
Standard |
copper core |
aluminum core |
VV-P YJV-P |
VLV-P YJLV-P |
Copper (aluminum) PVC insulation metal screening PVC jacketing power cable
Copper(aluminum) XLPE insulation metal screening PVC jacketing power cable
|
Enterprise Standard |
VV22-P YJV22-P |
VLV22-P YJLV22-P |
Copper (aluminum) PVC insulation metal screening steel strip armoring PVC jacketing power cable
Copper (aluminum) XLPE insulation metal screening steel strip armoring PVC jacketing power cable
|
VV32-P YJV32-P |
VLV32-P YJLV32-P |
Copper (aluminum) PVC insulation metal screening thin steel wire armoring PVC jacketing power cable
Copper (aluminum) XLPE insulation metal screening thin steel
|
VV42-P YJV42-P |
VLV42-P YJLV42-P |
Copper (aluminum) PVC insulation metal screening thick steel wire armoring PVC jacketing power cable
Copper (aluminum) XLPE insulation metal screening thick steel wire armoring PVC jacketing power cable
|
III. Specification
Type |
Rated voltage kV |
Number of core |
Nominal cross-section mm2 |
Copper Core |
ALUMINUM core |
VV-P. YJV-P |
VLV-P. YJLV-P |
0.6/1 |
1 2 3 4、3+1 |
4〜300 4〜185 4 〜300 4〜300 |
VV22-P、 YJV22-P |
VLV22-P、 YJLV22-P |
VV32-P、 YJV32-P |
VLV32-P. YJLV32-P |
VV42-P、 YJV42-P |
VLV42-P、 YJLV42-P |
IV. Structural Figure
V. Technical Parameter
1. Conductor DC resistance shall meet the stipulation in GB/T3956.
2. Finished cable shall pass the AC voltage (50Hz、5min、3500v) test without breakdown.
3. Insulation resistance
No |
Properties |
PVC insulation |
XLPE insulation |
1 |
p Volume resistivity Ω ・ cm 20°C Rating operating temperature 20°C of the cable |
1013 1010 |
— 1012 |
2 |
Ki Insulation resistance constant Ki MΩ - km 20°C Rating operating temperature 20°C of the cable |
36.7 0.037 |
— 3.67 |
Ⅵ. Feature
1. It has excellent properties for anti-electromagnetic interfere and anti-thunder damage.
2. It can balance the potential, and so improve the electricity quality.
http://www.baoshida-group.com/